| <<< PLC
types |
|
|
|
Specifications ALPHA XL
|
|
|
|
|
|
|
| General Operating
Conditions:
|
|
| Ambient temperature [°C] |
Display: -10 – 55 °C, Hardware: -25 – 55 °C |
|
| Operating temperature [°C] |
Display: -10 – 55 °C, Hardware: -25 – 55 °C |
|
| Storage temperature [%] |
-30 –+70 °C |
|
| Noise immunity |
1000 Vpp with noise generator; 1 µs at 30 – 100
Hz, tested by noise simulator |
|
| Dielectric withstand voltage |
3750 V AC, >1 min. according to EN60730 |
|
| Insulation resistance |
500 V DC, 7MOhm according to
EN60730-1 |
| Shosk resistance |
Acc. to IEC 68-2-27: 147 m/s2 acceleration, 11 ms 3
x 3 directions
|
|
| Vibration resistance |
Acc. to IEC-2-6: 19,6m/s2 acceleration,
80min. in each direction
|
|
| Acc. to IEC-2-6: 9.8 m/s2 acceleration,
80min. in each direction |
|
| Protection rating |
IP 20 |
|
| Grounding |
Not exist |
|
| Approvals |
UL/cUL |
|
| Tests |
UL 508; EN 60730-1; EN 61010-1; EN 50081-1;
EN 50082-1; EN 50082-2 |
|
|
|
|
|
|
|
|
|
|
Specifications
|
|
|
|
Specifications: |
AL2-14 MRA |
AL2-14 MRD |
AL2-24 MRA |
AL2-24 MRD |
| Electrical specifications: |
| Integrated inputs/outputs |
14 |
14 |
24 |
24 |
Power
supply |
AC range (+10%, -15 %) |
100-240 V AC |
24V DC |
100-240 V AC |
24V DC |
| Frequency at AC |
50-60 Hz |
- |
50-60 Hz |
- |
| Voltage fluctuation |
-15-+10% |
-15-+20% |
-15-+10% |
-15-+20% |
| Max. permissible voltage
drop time [ms] |
10 |
5 |
10 |
5 |
| Max. power consumption [W] |
5,5 |
7,5 |
7 |
9 |
Typ. power
consumption [W] |
All I/Os ON |
4,5 |
4 |
5,5 |
5 |
| All I/Os OFF |
2 |
1 |
2,5 |
1 |
| Inrush current
[A] |
<= 6,5 |
<= 7 |
<= 6,5 |
<= 7 |
| Digital inputs: |
| Integrated inputs |
8 |
8 |
15 |
15 |
| Input voltage |
100-240 V AC |
24V DC |
100-240 V AC |
24V DC |
| Input current [mA] |
0,24 |
5 |
0,24 |
5 |
| Response time [ms] |
50 |
10-20 |
50 |
10-20 |
| Input frequency
[Hz] |
5 |
20 |
5 |
20 |
| Analog inputs: |
| Channels |
- |
8 |
- |
8 |
| Analog input range
[V] |
- |
0-500 |
- |
0-500 |
| Resolution (x / 250mV) |
- |
9 bit, 20mV (10V,500) |
- |
9 bit, 20mV (10V,500) |
| Conversion speed
[ms] |
- |
8 |
- |
8 |
| Voltage
[V DC] |
- |
0-10 |
- |
0-10 |
| Impedance [KOhm] |
- |
142 ±5% |
- |
142 ±5% |
| Accuracy (0,5V DC) |
- |
± 5% |
- |
± 5% |
| Outputs: |
| Integrated outputs |
6 |
6 |
9 |
9 |
| Type |
Relay |
Relay |
Relay |
Relay |
| Switched voltage |
250V AC 30V DC |
250V AC 30V DC |
250V AC 30V DC |
250V AC 30V DC |
| Rated current [A] |
8 |
8 |
8 |
8 |
Max. switched
load
|
- inductive load |
373 VA |
373 VA |
373 VA * 93 VA ** |
373 VA * 93 VA ** |
| - resistive load |
- |
- |
- |
- |
| Minimum load |
50 mW |
50 mW |
50 mW |
50 mW |
| Response time [ms] |
<= 10 |
<= 10 |
<= 10 |
<= 10 |
| Leakage current |
- |
- |
- |
- |
| Relay contact lifetime
cycles [kapcsolás]
(8A) |
100.000 |
100.000 |
100.000 |
100.000 |
| Mechanical
specifications: |
| Weight [kg] |
0,3 |
0,3 |
0,35 |
0,3 |
| Dimensions (Wx H x
D) [mm] |
124,6 x 90 x 52 |
124,6 x 90 x 52 |
124,6 x 90 x 52 |
124,6 x 90 x 52 |
|
|
|
|
|
|
|
|
|
|
|