<<< PLC types |
|
|
|
|
|
|
|
|
|
Specifications ALPHA
|
|
|
|
|
|
|
|
|
|
| General Operating Conditions: |
|
| Ambient temperature [°C] |
0-55 |
|
| Operating temperature [°C] |
(-30)...70 |
|
| Allowable relative humidity [%] |
35-85 |
|
| Noise immunity |
1000 Vpp with noise generator; 1 µs at 30 – 100
Hz, tested by noise simulator |
|
| Dielectric withstand voltage |
3750 V AC, >1 min. according to EN60730 |
|
| Insulation resistance |
500 V DC, 7M?acc. to EN60730-1 |
|
| Vibration resistance |
direct mounting |
Acc. to IEC-2-6: 147 m/s2 acceleration, 80min. in each
direction
|
|
| DIN railmounting |
Acc. to IEC 68-2-27: 9.8 m/s2 acceleration, 80min. in
each direction
|
|
| Shock resistance |
Acc. to IEC 68-2-27: 147 m/s2 acceleration, 11ms 3 x 3 directions |
|
| Protection rating |
IP 20 |
|
| Grounding |
Not Recommended |
|
| Ambient conditions |
No corrosive gases, no dust |
|
| Approvals |
CE, UL/cUL, DNV |
|
| Tests |
UL 508, EN60730-1, EN61010, EN50081-1, EN50082-1, EN50082-2 |
|
|
|
|
|
|
|
|
|
|
|
Specifications
ALPHA
|
|
|
|
|
|
|
|
|
|
Specifications: |
AL6 - MRA |
AL10-MRA |
AL10-MRD |
AL10-MTD |
AL20-MRA |
AL20-MRD |
AL20-MTD |
| Electrical specifications: |
| Integrated inputs/outputs |
6 |
10 |
10 |
10 |
20 |
20 |
20 |
Power
supply |
AC range (+10%, -15 %) |
100-240 V AC |
100-240 V AC |
24V DC |
24V DC |
100-240 V AC |
24V DC |
24V DC |
| Frequency at AC |
50-60 Hz |
50-60 Hz |
- |
- |
50-60 Hz |
- |
- |
| Voltage fluctuation |
-15+10% |
-15+10% |
-15+20% |
-15+20% |
-15+10% |
-15+20% |
-15+20% |
| Max. permissible voltage
drop time [ms] |
10 |
10 |
5 |
5 |
10 |
5 |
5 |
| Max. power consumption
[W] |
3 |
4 |
3 |
2 |
8 |
7 |
5 |
Typ. power
consumption [W] |
All I/Os ON |
2,5 |
3 |
2 |
2 |
5 |
5 |
5 |
| All I/Os OFF |
1,5 |
1,5 |
0,3 |
0,3 |
1,5 |
0,3 |
0,3 |
| Inrush current
[A] |
<= 1,5 |
<= 1,5 |
<= 7 |
<= 7 |
<= 1,5 |
<= 7 |
<= 7 |
| Digital inputs: |
| Integrated inputs |
4 |
6 |
6 |
6 |
12 |
12 |
12 |
| Input voltage |
100-240 V AC |
100-240 V AC |
24V DC |
24V DC |
100-240 V AC |
24V DC |
24V DC |
| Input current [mA] |
0,24 |
0,24 |
5 |
5 |
0,24 |
5 |
5 |
| Response time [ms] |
50 |
50 |
10-40 |
10-40 |
50 |
10-40 |
10-40 |
| Input frequency
[Hz] |
5 |
5 |
20 |
20 |
5 |
20 |
20 |
| Analog inputs: |
| Channels |
- |
- |
6 |
6 |
- |
8 |
8 |
| Analog input range
[V] |
- |
- |
0-250 |
0-250 |
- |
0-250 |
0-250 |
| Resolution (x / 250mV) |
- |
- |
10000 |
10000 |
- |
10000 |
10000 |
| Conversion speed
[ms] |
- |
- |
10 |
10 |
- |
10 |
10 |
| Voltage
[V DC] |
- |
- |
0-10 |
0-10 |
- |
0-10 |
0-10 |
| Impedance [KOhm] |
- |
- |
< 150 |
< 150 |
- |
< 150 |
< 150 |
| Accuracy (0,5V DC) |
- |
- |
± 5% |
± 5% |
- |
± 5% |
± 5% |
| Outputs: |
| Integrated outputs |
2 |
4 |
4 |
4 |
8 |
8 |
8 |
| Type |
Relay |
Relay |
Relay |
Tranz. |
Relay |
Relay |
Tranz. |
| Switched voltage (max.) |
250V AC 30V DC |
250V AC 30V DC |
250V AC 30V DC |
5-24V DC |
250V AC 30V DC |
250V AC 30V DC |
5-24V DC |
| Rated current [A] (*=8-24VDC,
**=5-8V DC) |
8 |
8 |
8 |
1*,0,1** |
8 |
8 |
1*,0,1** |
Max. switched
load |
- inductive load |
- |
- |
- |
1A/24V DC |
- |
- |
1A/24V DC |
| - resistive load |
- |
- |
- |
3W/24V DC |
- |
- |
3W/24V DC |
| Minimum load |
50 mW |
50 mW |
50 mW |
1 mA |
50 mW |
50 mW |
1 mA |
| Response time [ms] |
<= 10 |
<= 10 |
<= 10 |
<= 1 |
<= 10 |
<= 10 |
<= 1 |
| Leakage current |
- |
- |
- |
<= 0,1 mA / 24V DC |
- |
- |
<= 0,1 mA / 24V DC |
| Relay contact lifetime
cycles
(8A) |
100.000 |
100.000 |
100.000 |
- |
100.000 |
100.000 |
- |
| Mechanical
specifications: |
| Weight [kg] |
0,2 |
0,2 |
0,2 |
0,2 |
0,32 |
0,32 |
0,32 |
| Dimensions (WxHxD) [mm] |
71,2 x 90 x 55 |
71,2 x 90 x 55 |
71,2 x 90 x 55 |
71,2 x 90 x 55 |
124,6 x 90 x 55 |
124,6 x 90 x 55 |
124,6 x 90 x 55 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
 |
|