| General
Specifications: |
| Ambient temperature
[°C] |
0-55 |
| Operating temperature
[°C] |
0-55 |
| Storage temperature
[°C] |
-20...+70 |
| Primary power supply |
24 V DC, 400 mA; ripple ratio at maximum load:=±5% |
| Protection |
IP 20 |
| Noise durability |
1000 Vpp with noise generator; 1 µs at
30 – 100 Hz |
| Dielectric withstand voltage |
1500 V AC, 1min. (500 V AC for direct voltage
modules) |
| Ambient relative humidity |
35 - 85% |
| Shock resistance |
Acc. to IEC 68-2-27 (15 G (3 times each in 3
directions for 11 ms)) |
| Vibration resistance |
Acc. to IEC 68-2-6 (1 G: resistance to vibrations
from 57 – 150 Hz for 80 minutes along all
3 axes; 0.5 G for DIN railmounting |
| Insulation resistance |
500V DC, 5MOhm |
| Ground |
Class 3 |
| Fuse |
3A |
| Environment |
Avoid environments containing corrosive gases,
install in a dust-free location. |
| Certifications |
UL/CSA/CE/LR/DNV , RINA/BV/GL/ECE |
| System
Specifications: |
| Program
data: |
| Program memory |
2.000 steps EEPROM (internal) |
| Program execution |
Periodical execution of the stored program |
| Program protection |
Password protection with 3 protection levels |
| Number of instructions |
29 sequence instructions, 2 step ladder instructions,
89 applied instructions |
| Cycle period |
0.55 – 0.7 µs / log. instruction |
| Operands: |
| Internal relays |
512 total, with 384 general (M0 –M383)
and 128 buffered (M384 –M511) |
| Special relays |
256 (M8000 –M8255) |
| Step relays |
128 |
| Timers |
63 (max. 63 timers, partially switchable to 100
ms, 10ms and 1ms) |
| External setpoint entry via potentiometer |
2 potentiometers |
| Counter |
32 (16 bit), C0 – C31 |
| High-speed counter inputs |
1 phase: 6 input for max. 60 kHz, 2 phases: 2
inputs for max. 30 kHz |
| Data register |
256 subtotal (128 common (D0 – D127) and
128 buffered (D128 – D255)) |
| Index register |
16 |
| Special register |
256 (16 bit) (D8000-D8255) |
| Pointer |
64 (P0-P63) |
| Nesting operands |
8 (N0-N7) |
| Interrupt inputs |
6 |
| Constants |
16 bit: K: -32,768...+32,767;
hex: 0...FFFF |
| 32 bit: K: -2,147,483,648...+2,147,483,647;
hex: 0...FFFF FFFF |
|
|
|
| |
Specifications
of Base Units |
Specifications: |
FX-1S 10MR-DS |
FX-1S 10MR-ES-UL |
FX-1S 10MT-DSS |
FX-1S 10MT-ESS-UL |
FX-1S 14MR-DS |
FX-1S 14MR-ES-UL |
FX-1S 14MT-DSS |
FX-1S 14MT-ESS-UL |
| Elektrical
data: |
| Max. number inputs/outputs |
10 |
10 |
10 |
10 |
14 |
14 |
14 |
14 |
| Power
supply |
AC (+10%, -15%) |
- |
100-240 V AC |
- |
100-240 V AC |
- |
100-240 V AC |
- |
100-240 V AC |
| Frequency at
AC [Hz] |
- |
50-60 (± 10%) |
- |
50-60 (± 10%) |
- |
50-60 (± 10%) |
- |
50-60 (± 10%) |
| DC (+10%, -15%) |
24V DC |
- |
24V DC |
- |
24V DC |
- |
24V DC |
- |
| Max.
input apparent power. [W] |
6 |
19 |
6 |
19 |
6,5 |
19 |
6,5 |
19 |
Inrush
current
at ON
[A] |
100V AC |
- |
15A/5ms |
- |
15A/5ms |
- |
15A/5ms |
- |
15A/5ms |
| 200V AC |
- |
25A/5ms |
- |
25A/5ms |
- |
25A/5ms |
- |
25A/5ms |
| 24V DC |
15A/0,1 ms |
- |
15A/0,1 ms |
- |
15A/0,1 ms |
- |
15A/0,1 ms |
- |
| Allowable
momentary power failure time [ms] |
5 |
10 |
5 |
10 |
5 |
10 |
5 |
10 |
| External
current supply. (24V DC) [mA] |
- |
400 |
- |
400 |
- |
400 |
- |
400 |
| Inputs: |
| Integrated inputs |
6 |
6 |
6 |
6 |
8 |
8 |
8 |
8 |
| Min.
current for logical 1 [mA] X0...X7
/ X10...X30 |
4,5 / 3,5 |
4,5 / 3,5 |
4,5 / 3,5 |
4,5 / 3,5 |
4,5 / 3,5 |
4,5 / 3,5 |
4,5 / 3,5 |
4,5 / 3,5 |
| Max.
current for logical 0[mA] |
1,5 |
1,5 |
1,5 |
1,5 |
1,5 |
1,5 |
1,5 |
1,5 |
| Response
time
[ms] |
For all units of the MELSEC FX1S series
values: 10 ms (at time of shipping), adjustable
from 0 to 15 ms in steps of 1 ms. |
| Outputs: |
| Integrated outputs |
4 |
4 |
4 |
4 |
6 |
6 |
6 |
6 |
| Output |
Relay |
Relay |
Tranz. |
Tranz. |
Relay |
Relay |
Tranz. |
Tranz. |
| Switching voltage (max.) |
Generally for relay version:<250
V AC,<30 V DC; for transistor version: 5 – 30
V DC |
Max. output
current [A] |
- per output |
2 |
2 |
0,5 |
0,5 |
2 |
2 |
0,5 |
0,5 |
| - per group* |
8 |
8 |
0,8 |
0,8 |
8 |
8 |
0,8 |
0,8 |
Max. switching
current |
- inductive load |
80VA |
80VA |
12W |
12W |
80VA |
80VA |
12W |
12W |
- lamp load |
100W |
100W |
0,9W |
0,9W |
100W |
100W |
0,9W |
0,9W |
| Response
time
[ms] |
10 |
10 |
0,2 |
0,2 |
10 |
10 |
0,2 |
0,2 |
| Life of contacts (switching
times) |
3,000,000 (at
20VA); 1,000,000 (at 35VA); 200,000 (at 80VA) |
| Mechanical
data: |
| Weight
[kg] |
0,22 |
0,3 |
0,22 |
0,3 |
0,22 |
0,3 |
0,22 |
0,3 |
| Dimensions
(WxHxD) [mm] |
60 x 90 x 49 |
60 x 90 x 75 |
60 x 90 x 49 |
60 x 90 x 75 |
60 x 90 x 49 |
60 x 90 x 75 |
60 x 90 x 49 |
60 x 90 x 75 |
|
|
|
|
|
|
|
|
|
|
|
| |
Specifications
of Base Units |
Specifications: |
FX-1S 20MR-DS |
FX-1S 20MR-ES-UL |
FX-1S 20MT-DSS |
FX-1S 20MT-ESS-UL |
FX-1S 30MR-DS |
FX-1S 30MR-ES-UL |
FX-1S 30MT-DSS |
FX-1S 30MT-ESS-UL |
| Elektrical
data: |
| Max. number inputs/outputs |
20 |
20 |
20 |
20 |
30 |
30 |
30 |
30 |
Power
supply |
AC (+10%, -15%) |
- |
100-240 V AC |
- |
100-240 V AC |
- |
100-240 V AC |
- |
100-240 V AC |
| Frequency at [Hz] |
- |
50-60 (± 10%) |
- |
50-60 (± 10%) |
- |
50-60 (± 10%) |
- |
50-60 (± 10%) |
| DC (+10%, -15%) |
24V DC |
- |
24V DC |
- |
24V DC |
- |
24V DC |
- |
| Max. input apparent
power.
[W] |
7 |
20 |
7 |
20 |
8 |
21 |
8 |
21 |
Inrush
current
at ON
[A] |
100V AC |
- |
15A/5ms |
- |
15A/5ms |
- |
15A/5ms |
- |
15A/5ms |
| 200V AC |
- |
25A/5ms |
- |
25A/5ms |
- |
25A/5ms |
- |
25A/5ms |
| 24V DC |
15A/0,1 ms |
- |
15A/0,1 ms |
- |
15A/0,1 ms |
- |
15A/0,1 ms |
- |
| Allowable momentary
power failure time [ms] |
5 |
10 |
5 |
10 |
5 |
10 |
5 |
10 |
| External current supply
(24 V DC) [mA] |
- |
400 |
- |
400 |
- |
400 |
- |
400 |
| Inputs: |
| Integrated inputs |
12 |
12 |
12 |
12 |
16 |
16 |
16 |
16 |
| Min. current for logical
1 [mA] X0...X7 / X10...X30 |
4,5 / 3,5 |
4,5 / 3,5 |
4,5 / 3,5 |
4,5 / 3,5 |
4,5 / 3,5 |
4,5 / 3,5 |
4,5 / 3,5 |
4,5 / 3,5 |
| Max. current for logical
0 [mA] |
1,5 |
1,5 |
1,5 |
1,5 |
1,5 |
1,5 |
1,5 |
1,5 |
| Response time [ms] |
10 ms (1-15 ms adjustable
in 1ms steps), to all MELSEC FX-1S |
| Outputs: |
| Integrated outputs |
8 |
8 |
8 |
8 |
14 |
14 |
14 |
14 |
| Output |
Relay |
Relay |
Tranz. |
Tranz. |
Relay |
Relay |
Tranz. |
Tranz. |
| Switching voltage (max.) |
Generally for relay
version: > 250V AC, > 30V DC; for tranzistorversion:
5-30V DC |
Max. output
current [A] |
- per output |
2 |
2 |
0,5 |
0,5 |
2 |
2 |
0,5 |
0,5 |
| - per group* |
8 |
8 |
0,8 |
0,8 |
8 |
8 |
0,8 |
0,8 |
Max. switching
current
[A] |
- inductive load |
80VA |
80VA |
12W |
12W |
80VA |
80VA |
12W |
12W |
- lamp load |
100W |
100W |
0,9W |
0,9W |
100W |
100W |
0,9W |
0,9W |
| Response time [ms] |
10 |
10 |
0,2 |
0,2 |
10 |
10 |
0,2 |
0,2 |
| Life of contacts (switching times) |
3,000,000 (at 20VA);
1,000,000 (at 35VA); 200,000 (at 80VA) |
| Mechanical
data: |
| Weight [kg] |
0,3 |
0,4 |
0,3 |
0,4 |
0,35 |
0,45 |
0,35 |
0,45 |
| Dimensions (WxHxD)
[mm] |
75 x 90 x 49 |
75 x 90 x 75 |
75 x 90 x 49 |
75 x 90 x 75 |
100 x
90 x 49 |
100 x
90 x 75 |
100 x
90 x 49 |
100 x
90 x 75 |
|
|