General Specifications:

Ambient temperature [°C] 0-55
Operating temperature [°C] 0-55
Storage temperature [°C] -20...+70
Service power supply 24 V DC, 400 mA (FX1N); 250/460 mA (FX2N/FX2NC) ripple ratio at maximum load:=±5%
Protection IP 20
Noise durability 1000 Vpp with noise generator; 1 ms at 30 – 100 Hz
Dielectric withstand voltage 1,500 V AC, 1min.
Ambient relative humidity 35 - 85%
Shock resistance FX2N/FX2NC: 2 G (resistance to vibrations from 10 – 55 Hz for 2 hours along all 3 axes; 0.5 G for DIN railmounting
Vibration resistance Acc. to IEC 68-2-6 (1 G: resistance to vibrations from 57 – 150 Hz for 80 minutes along all 3 axes; 0.5 G for DIN railmounting
Insulation resistance 500V DC, 5MOhm
Ground Class 3
Fuse Up to FX1N-24: 1 A; from FX1N-40: 3 A; from FX2N-32: 3.15 A; fromFX2N-48: 5 A; FX2NC-16MR-T-DS: 2.5 A; FX2NC-MT-DSS: 3.15
Environment Avoid environments containing corrosive gases, install in a dust-free location.
Certifications UL/CSA/CE/LR/DNV/GL/RINA; ECE
System specifications:
Program data:
I/O points (addresses) 256
Address range Max. 248 inputs X0–X367, max. 248 outputs Y0–Y367
Program memory 8,000 steps RAM (internal),
4,000 steps EPROM/EEPROM cassettes (optional),
16,000 steps RAM cassettes (optional),
16,000 steps EEPROM cassettes (optional)
Cycle period 0.08 µs / logical instruction
Programming language Step ladder, instruction list, SFC
Program execution Cyclical execution, refresh mode processing
Program protection Password protection with 3 protection levels
Number of instructions 27 sequence instructions, 2 step ladder instructions, 18 verify instructions,
107 applied instructions
Operands:
Internal relays 3072
Special relays 256 (M8000-M8255)
Step ladder 1000
Timer 256
Ext. preset value via potentiometer -
Counter 235 ; C0-C199 (16 bit), C200-C219 (32 bit)
High-speed counter 6 single phase inputs (max. 60 kHz), 2 double phase inputs (max. 30 kHz)
Real-time clock Year,month, day, hour, minut, second, weekday (FX2NC optionally)
Data register 8000 (D0-D7999)
File register Max . 7,000 (parameter editable), Total registers=8,000
Index register 16
Special register 256 (16 bit) (D8000-D8255)
Pointer 128 (P0-P127)
Nestings 8 (N0-N7)
Interrupt inputs 6
Constants 16 bit: K: -32,768...+32,767; hex: 0...FFFF
32 bit: K: -2,147,483,648...+2,147,483,647; hex: 0...FFFF FFFF
32 bit lebegopontos: 0; ±1,175 x 10-38.....±3.403 x 10-38
 

 

Specifications:

FX-2N 16MR-DS FX-2N 16MR-ES-UL FX-2N 16MT-DSS FX-2N 16MT-ESS-UL FX-2N 32MR-DS FX-2N 32MR-ES-UL FX-2N 32MT-DSS FX-2N 32MT-ESS-UL
Electrical data:
Integrated inputs/outputs 16 16 16 16 32 32 32 32
Power
supply
AC (+10%, -15%) - 100-240 V AC - 100-240 V AC - 100-240 V AC - 100-240 V AC
Frequency at AC [Hz] - 50-60 (± 10%) - 50-60 (± 10%) - 50-60 (± 10%) - 50-60 (± 10%)
DC (+20%, -30%) 24V DC - 24V DC - 24V DC - 24V DC -
Max. input apparent power 25W 30VA 25W 30VA 25W 40VA 25W 40VA
Inrush
current at ON[A]
100V AC - 40A<5 ms - 40A<5 ms - 40A<5 ms - 40A<5 ms
200V AC - 60A<5 ms - 60A<5 ms - 60A<5 ms - 60A<5 ms
Allowable momentary power failure time [ms] 5 10 10  10  10 
External service power supply (24V DC) [mA]  - 250  - 250  - 250  - 250
Power supply int. bus (5V DC) [mA] 290 290 290 290 290 290 290 290
Inputs:
Integrated inputs 8 8 8 8 16 16 16 16
Input current [mA] X0...X7 / X10...X** 7 / 5 7 / 5 7 / 5 7 / 5 7 / 5 7 / 5 7 / 5 7 / 5
Min. current for logical 1 [mA] X0...X7 / X10...X** 4,5 / 3,5 4,5 / 3,5 4,5 / 3,5 4,5 / 3,5 4,5 / 3,5 4,5 / 3,5 4,5 / 3,5 4,5 / 3,5
Max. current for logical 0 [mA] 1,5 1,5  1,5 1,5 1,5  1,5  1,5  1,5 
Isolation [ms] Photocoupler isolation between input terminals and PC power for all base units.
Response time For all base units of the MELSEC FX2N series: 10 ms (at time of shipment), partly adjustable between 0 and 15 ms (REFF, FNC51=0 – 60 ms)
Outputs:   
Integrated outputs 8 8 8 8 16 16 16 16
Output type Relay Relay Tranz. Tranz.  Relay Relay Tranz.  Tranz. 
ON voltage (max.) Generally for relay version:<250 V AC,<30 V DC; for transistor version: 5 – 30 V DC

Max. output
current [A]

*= at Y0 and Y1 : 0,3A

**=0,8A for four, 1,6A for eight groups

- per output 2 0,5 *  0,5 * 0,5 * 0,5 *
- per group* 8 0,8 ** 0,8 ** 8 0,8 ** 0,8 **
Max. switching
power[A]
- inductive load 80VA 80VA  12W 12W  80VA  80VA 12W  12W 

- lamp load

100W 100W  1,5W 1,5 100W  100W 1,5 1,5
Response time [ms] 10 10  <0,2  <0,2  10  <0,2  <0,2  <0,2 
Life of contacts (switching times) For all base units of the MELSEC FX2N series: 3,000,000 at 20 VA; 1,000,000 at 35 VA; 200,000 at 80 VA
Mechanical data:          
Weight [kg] 0,6 0,6 0,6 0,6 0,65 0,65  0,65 0,65
Dimensions (Wx H x D) [mm] 130 x 90 x 87 130 x 90 x 87 130 x 90 x 87 130 x 90 x 87 150 x 90 x 87 150 x 90 x 87  150 x 90 x 87 150 x 90 x 87

 

 

Base Units

Specifications:

FX-2N 48MR-DS FX-2N 48MR-ES-UL FX-2N 48MT-DSS FX-2N 48MT-ESS-UL FX-2N 64MR-DS FX-2N 64MR-ES-UL FX-2N 64MT-DSS FX-2N 64MT-ESS-UL
Electrical data:
Integrated inputs/outputs 48 48 48 48 64 64 64 64
Power supply AC (+10%, -15%) - 100-240 V AC - 100-240 V AC - 100-240 V AC - 100-240 V AC
Frequency at AC [Hz] - 50-60 (± 10%) - 50-60 (± 10%) - 50-60 (± 10%) - 50-60 (± 10%)
DC (+20%, -30%) 24V DC - 24V DC - 24V DC - 24V DC -
Max. input apparent power 30W 50VA 30W 50VA 35W 60VA 35W 60VA
Inrush
current at ON [A]
100V AC - 40A<5 ms - 40A<5 ms - 40A<5 ms - 40A<5 ms
200V AC - 60A<5 ms - 60A<5 ms - 60A<5 ms - 60A<5 ms
Allowable momentary power failure time [ms] 5 10 10  10  10 
External service power supply. (24V DC) [mA]  - 460  - 460  - 460  - 460
Power supply int. bus (5V DC) [mA] 290 290 290 290 290 290 290 290
Inputs:
Integrated inputs 24 24 24 24 32 32 32 32
Input current [mA] X0...X7 / X10...X** 7 / 5 7 / 5 7 / 5 7 / 5 7 / 5 7 / 5 7 / 5 7 / 5
Min. current for logical 1 [mA] X0...X7 / X10...X** 4,5 / 3,5 4,5 / 3,5 4,5 / 3,5 4,5 / 3,5 4,5 / 3,5 4,5 / 3,5 4,5 / 3,5 4,5 / 3,5
Max. current for logical 0 [mA] 1,5 1,5  1,5 1,5 1,5  1,5  1,5  1,5 
Response time [ms] For all base units of the MELSEC FX2N series: 10 ms (at time of shipment), partly adjustable between 0 and 15 ms (REFF, FNC51=0 – 60 ms)
Isolation Photocoupler isolation between input terminals and PC power for all base units.
Outputs:   
Integrated outputs 24 24 24 24 32 32 32 32
Output type Relay Relay Tranz. Tranz.  Relay Relay Tranz.  Tranz. 
ON voltage (max.) Generally for relay version:<250 V AC,<30 V DC; for transistor version: 5 – 30 V DC

Max. output current [A]

 

- per output 2 0,5 *  0,5 * 0,5 * 0,5 *
- per group* 8 0,8 ** 0,8 ** 8 0,8 ** 0,8 **
Max. switching
power [A]
- inductive loadl 80VA 80VA  12W 12W  80VA  80VA 12W  12W 

- lamp load

100W 100W  1,5W 1,5 100W  100W 1,5 1,5
Response time [ms] 10 10  <0,2  <0,2  10  10 <0,2  <0,2 
Life of contacts (switching times) For all base units of theMELSEC FX2N series: 3,000,000 at 20 VA; 1,000,000 at 35 VA; 200,000 at 80 VA
Mechanical data:          
Weight [kg] 0,85 0,85 0,85 0,85 1,0 1,0 1,0 1,0
Dimensions (Wx H x D) [mm] 182 x 90 x 87 182 x 90 x 87 182 x 90 x 87 182 x 90 x 87 220 x 90 x 87 220 x 90 x 87  220 x 90 x 87 220 x 90 x 87
 

Base Units

Specifications:

FX-2N 80MR-DS FX-2N 80MR-ES-UL FX-2N 80MT-DSS FX-2N 80MT-ESS-UL FX-2N 128MR-ES-UL FX-2N 128MT-ESS-UL
Electrical data
Integrated inputs/outputs 80 80 80 80 128 128
Power supply AC (+10%, -15%) - 100-240 V AC - 100-240 V AC 100-240 V AC 100-240 V AC
Frequency at AC [Hz] - 50-60 (± 10%) - 50-60 (± 10%) - 50-60 (± 10%)
DC (+20%, -30%) 24V DC - 24V DC - - -
Max. input apparent power 40W 70VA 40W 70VA 100VA 100VA
Inrush current at ONl [A] 100V AC - 40A<5 ms - 40A<5 ms 50A<7 ms 50A<7 ms
200V AC - 60A<5 ms - 60A<5 ms 70A<7 ms 70A<7 ms
Allowablemomentary power failure time [ms] 5 10 10  10 10 
External service power supply. (24V DC) [mA]  - 460  - 460 460 460
Power supply int. bus (5V DC) [mA] 290 290 290 290 290 290
Inputs:
Integrated inputs 40 40 40 40 64 64
Input current [mA] X0...X7 / X10...X** 7 / 5 7 / 5 7 / 5 7 / 5 7 / 5 7 / 5
Min. current for logical 1 [mA] X0...X7 / X10...X** 4,5 / 3,5 4,5 / 3,5 4,5 / 3,5 4,5 / 3,5 4,5 / 3,5 4,5 / 3,5
Max. current for logical 0 [mA] 1,5 1,5  1,5 1,5 1,5  1,5 
Response time [ms] For all base units of theMELSEC FX2N series: 10 ms (at time of shipment), partly adjustable between 0 and 15 ms (REFF, FNC51=0 – 60 ms)
Isolation Photocoupler isolation between input terminals and PC power for all base units.
Outputs:   
Integrated outputs 40 40 40 40 64 64
Output type Relay Relay Tranz. Tranz.  Relay Tranz.
ON voltage (max.) Generally for relay version:<250 V AC,<30 V DC; for transistor version: 5 – 30 V DC

Max. output
current [A]

 

- per output 2 0,5 *  0,5 * 0,5 *
- per group* 8 0,8 ** 0,8 ** 8 0,8 **
Max. switching
power [A]
- inductive load 80VA 80VA  12W 12W 80VA  12W

- lamp load

100W 100W  1,5W 1,5 100W  1,5W
Response time [ms] 10 10  <0,2  <0,2  10  <0,2
Life of contacts (switching times) For all base units of the MELSEC FX2N series: 3,000,000 at 20 VA; 1,000,000 at 35 VA; 200,000 at 80 VA
Mechanical data:          
Weight [kg] 1,2 1,2 1,2 1,2 1,8 1,8
Dimensions (Wx H x D) [mm] 285 x 90 x 87 285 x 90 x 87 285 x 90 x 87 285 x 90 x 87 350 x 90 x 87 350 x 90 x 87 
 


Axicont Ltd is the authorised Distributor for Mitsubishi Electric products in Hungary.